Transformer sizing begins with the actual coincident operating load—not the sum of every connected nameplate and not a rule-of-thumb margin alone. Convert the expected demand into kVA, then verify starting duty, harmonics, ambient conditions, voltage regulation, short-circuit requirements, redundancy and credible future growth.

The calculated kVA is a starting point. The approved load schedule, system studies, project specification and quotation-stage transformer datasheet govern the final rating.

1. Define the transformer duty

First establish whether the transformer supplies a building, process line, workshop or mixed load; whether it operates continuously or intermittently; whether it must start large motors; and whether another transformer provides redundancy. The same connected kW can require a different transformer when the operating sequence changes.

Normal, standby or cyclic duty
Maximum coincident load
Largest motor and starting method
Nonlinear and single-phase loads
Parallel-operation requirement
Approved expansion stages

2. Build the load schedule

Group loads by type and record connected rating, demand or simultaneity, power factor, motor efficiency where relevant, duty cycle and harmonic information. Do not apply one diversity factor without understanding which loads can operate together.

Load groupRecordWhy it matters
Lighting and small powerConnected kW, demand factor, PFUsually aggregated, but operating hours and nonlinear share may differ.
MotorsShaft kW, efficiency, PF, starting methodRunning input and starting voltage dip both require review.
UPS, VFD and rectifier loadskW/kVA, true PF, harmonic dataHarmonic current can increase heating and neutral current.
Future loadsRating and planned dateProvides a traceable growth allowance instead of an arbitrary percentage.

3. Convert demand to kVA

Electrical load stated in input kWRequired kVA = demand kW / power factorMotor stated by mechanical shaft outputMotor input kVA = shaft kW / (efficiency × power factor)

Add coincident contributions. Where groups have substantially different power factors, the electrical designer may use a complex-power calculation rather than simply adding kVA.

Worked preliminary example

A facility has 300 kW of general connected load with a justified demand factor of 0.75 and expected PF of 0.90. A 90 kW motor runs simultaneously at 94% efficiency and PF 0.88. A documented near-term expansion allowance of 15% is applied.

CalculationGeneral demand: 300 × 0.75 / 0.90 = 250 kVA Motor input: 90 / (0.94 × 0.88) ≈ 109 kVA Present demand: 250 + 109 = 359 kVA With 15% expansion: 359 × 1.15 ≈ 413 kVA

A 500 kVA standard rating may be a candidate, but it is not final until the following checks are complete.

4. Check what the kVA total misses

Motor starting and voltage dip

Running kVA does not prove that a motor can start without an unacceptable dip. Review locked-rotor or starting current, acceleration time, starting method, transformer impedance, upstream source impedance, cable impedance and the sensitivity of other connected loads.

Harmonic loads

UPS systems, drives, rectifiers and chargers can add winding and stray losses. Provide the load type, true power factor and current harmonic spectrum or THDi where available. Selecting the next standard kVA alone does not resolve a harmonic-duty question.

Ambient and installation

State temperature, altitude, indoor/outdoor location, enclosure, ventilation, direct sun, dust, salt, humidity and seismic conditions. A dry-type enclosure or restricted airflow can change thermal capability; non-standard conditions may require a design adjustment.

Growth and redundancy

Tie growth margin to a real expansion plan. One large transformer may simplify the installation, while two units can provide staging or redundancy. Compare part-load losses, switching arrangement, fault level, civil space and the load that must remain available during an outage.

5. Complete the electrical specification

ItemConfirm
Voltage and frequencyRated HV/LV, highest system voltage where applicable, and 50/60 Hz duty.
Vector group and neutralPhase displacement, neutral availability, earthing and parallel compatibility.
TapsRange, steps and whether off-circuit or on-load operation is required.
ImpedanceFault current, voltage regulation and parallel load sharing.
Construction and coolingOil-immersed, cast-resin dry type or project-specific arrangement and cooling stage.
Loss scheduleGuaranteed no-load and load loss for the exact rating, reference temperature and applicable standard.
DocumentsApplicable standards, drawings, test records and destination-market requirements.

6. Avoid common sizing mistakes

  • Adding every nameplate at 100% when loads are mutually exclusive.
  • Applying diversity again to a measured maximum demand that already reflects simultaneity.
  • Using motor shaft kW as electrical input kW.
  • Ignoring motor starting, harmonics or ambient conditions.
  • Adding vague future margin without checking the switchboard, cables and protection.
  • Selecting by transformer series number instead of the approved parameter and loss schedule.

Information for a technical inquiry

Destination and application
Single-line diagram
HV, LV and frequency
Load schedule and maximum demand
Motor starting information
Harmonic load information
Ambient, altitude and enclosure
Vector group, taps and impedance
Accessories and cable arrangement
Required standards and documents

Catalogue ranges support initial screening. The approved quotation-stage datasheet and project studies should determine the final procurement rating.